Single-phase electric energy meter

 
Single-phase electric energy meter - CE200 case modification – S4

CE200

case modification – S4
TOR 4228-056-22136119-2006
Single-phase two-element “CE” line electricity meter.
For board mounting.
Designed for active energy measurement in single-phase alternating current circuits.
Maximum protection against connection manipulation.
 
  Standard compliance
 
  • Complies with GOST R 52320-2005.
  • Complies with GOST R 52322-2005.
  • Certified and listed in the RF State Register of Measurement Facilities.
  Specifications
 
Items Values
Accuracy class 1; 2
Rate quantity 1
Measuring network frequency, Hz 50±2.5
Nominal voltage, V 230
Basic (maximum) current, A 5 (60)
Starting current, A 0.02
Consumed power in parallel circuit, not more than, V*A (W) 9 (0.6)
Full consumed power in series circuit, not more than, V*A 0.1
Pulse telemetric output transmission ratio, imp./kW*h 800; 1600; 3200
Operating temperature range, °C from - 40 to 70
Overall dimensions, not more than, mm 185 x 120.5 x 61.5
Weight, not more than, kg 0.5
  Peculiar features
 
  • High theft protection.
  • Two measuring elements.
  • Low energy consumption.
  • Standard and optical telemetric outputs.
  • Light indicator of meter operation.
  • Mechanical or electronic summator.
  • Resistance to environmental, mechanical and electromagnetic influence.
  Reliability characteristics
 
  • Minimum time to failure — 160 000 hours.
  • Calibration interval — 16 years.
  • Average service life — 30 years.
  • Warranty period — 5 years.
  Overall dimensions
  CE200 - Single-phase electricity meter
  Designation structure
  CE200 X X X X X
Register type:
M - mechanical;
(no letters) - LCD.
Basic (maximum) current
5 - 5 (60)A.
Nominal voltage
4 - 230V.
Accuracy class according to GOST R 52322-2005:
1 - 1;
2 - 2
Case type
S4 - for board mounting.
Note: number indicates case modification.
  Documentation
 
  Operating manual PDF 283 kB