PRODUCTS CONTACTS SERVICE
add favorite JSC "Concern Energomera"Sate mapconcern@energomera.runews@energomera.ru
 RU  |  PL
ABOUT COMPANY INVESTORS TRAINING EXHIBITIONS & SEMINARS SERVICE PRODUCTS

» Verification (Calibration) sets

» Electric Energy Meter Calibrators

» Portable Metrological Equipment

» ENERGOMERA CE602

» ENERGOMERA CE601

» CE6815

» CE6806P

» Standard Meters

» Accessories

.: ENERGOMERA TM
    PRODUCTS

» Electricity meters

» Automatic Meter Reading Systems

» Switchboards

» Low Voltage Products

» Telecommunication cabinets

» Electrochemical Protection Equipment

 

Single-phase portable standard meter

 
ENERGOMERA SÅ601 - Single-phase portable standard meter
ENERGOMERA SE601
TOR 4381-041-46146329-2003
Provides verification and calibration of electronic and induction-type single-phase active electricity meters in laboratory and working environment. Determines meter's error at the place of installation. Measures signals' parameters in the circuit under test.
 
  NORMATIVE-LEGAL SUPPORT
 
  • Compliance with the GOST 22261 "Means for measuring electrical and magnetic quantities. General specifications"
  • Certified in Russia and CIS
  SPECIFICATIONS
  Items Values
  Basic relative error at verified meters inaccuracy test, %
from ±0,5
  Basic relative error at measurement of
- voltage, %
- current strength, %

±1,0
±1,0
  Basic absolute error at measurement of
- active power factor
- input signal frequency, Hz

±0,01
±0,1
  Input signal range of:
- voltage, V
- current strength, A

125-250
0,1-100
  Input signal frequency range, Hz
47,5-52,5
  Active power factor measurement range
from minus 1 up to 1
  Power consumption, V*A, not more than
7
  Overall dimensions, mm, not more than:
— length
— width
— height

230
110
50
  Weight, kg, not more than
0,5
 
  PECULIAR FEATURES
 
  • Carrying out of measurements without breaking current circuit by means of clamp-on-meter (0,1-100)A
  • Accuracy class of verified active energy meters - 2,0 and of less precision.
  • Measurement of basic electrical power values of the circuit under control with possibility of display of measurement results on standard meter panel.
  • Availability of photosensing head for induction-type meters' verification.
  • Possibility of saving of meters' verification results and signals' parameters in the circuits under control in permanent memory with further transmission into PC via RS232 interface.
  • The set includes upper-level software, allowing automatization of gathering and registration of verification protocols.
  • Power is supplied from the circuit under control (voltage range 125-250V)
  • Working temperature range is from minus 20 up to 50°C
  • Possibility of phase-by-phase checking of proper connection of three-phase meters (by the measured power factor values)
 
  RELIABILITY CHARACTERISTICS
 
  • Verification interval - 2 years
  • Warranty - 1,5 years
 
  MODIFICATIONS
 
  • ENERGOMERA SE601-05 - standard;
  • ENERGOMERA SE601-05R - expanded set of spare parts and instruments (completed with the bag and additional pinchers of "crocodile" type for connecting to the voltage circuit under control).
 
  DOCUMENTATION
  Operating manual PDF 319 KB
  Technical passport PDF 369 KB

Go top
ABOUT COMPANY NEWS TRAINING PUBLICATIONS IN MASS MEDIA SERVICE PRODUCTS
© 2001-2010 Concern Energomera JSC