OIN |
|
|
| PMEA 656111.011 TU |
|
Protection of electrical equipment and household devices against lightning surges and surge voltages.
|
|
|
| |
|
|
|
|
| |
- Compliance with the GOST 12.1.007.0 "Occupational safety standards system. Noxious substances. Classification and general requirements", other standards and PUE.
- Limiters application necessity - by p.7.1.22 PUE-7.
- Requirements to overvoltage protection - by the GOST R 50571.19-2000 (IEC 60364-4-443-95)
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| |
- Max. continuous operating voltage - 275V, frequency - 50Hz.
- At 275V voltage operating consumption current does not exceed 0,7mA.
- Unified module (17,5 mm width) for mounting on a rail (35/7mm).
- Withstands complex wave impulses at 10,0kV open-circuit voltage and 5 kV short-circuit current.
- Provides protection of equipment against impulse resistance of category II
(GOST R 50571.19-2000) (voltage level).
- Withstands undamaged temporary overvoltage of 380V.
- Conductors (sections from 4 up to 16mm) can be connected.
|
|
|
|