RESIDUAL CURRENT PROTECTIVE DEVICE (RCD)
|
|
|
|
| |
 |
RCD-VAD2 three-phase |
|
|
| 656111.001 TOR |
Protection against electric-shock hazard
Rated currents - up to 63A
Central location on the rail
Wide range of versions, including versions with extended functional capabilities
|
|
|
|
|
|
|
| |
- Compliance with the GOST R 51327.1-99, GOST R 51327.2.2-99, GOST R 51329-99, GOST R 51992-2002 "Occupational safety standards system. Earth leakage circuit breakers. Classification. General technical requirements", PUE and GlavGosenergonadzor (State Energy Inspection directives) of Russia on RCD application, and also fire safety regulations NPB 243-97
- Certificate of compliance
- Certificate of fire safety
|
|
|
|
|
|
| |
- Wide range of load currents and breaking differential currents.
- Improved make-and-break capability of load current and differential current.
- Optimal structure of the device providing connection of power supply circuit to the upper RCD clamps, and load - to the lower ones.
- Central location of meters on the rail - symmetrical in relation to the front side.
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
- Provide break both at sine alternating and direct pulse differential current (type A)
- Has built-in overcurrents protectors, provide automatic switch-off at 1.45 In overloads within 1 hour and at 10 In short circuit currents within 0.1 s.
- Able to function at ultimate range of supply line voltages from 110 up to 264V.
- Tolerable range of working temperatures is from -45 ... +55°C.
- Keeping of sensitivity at a repeated earthing of neutral main conductor.
- Possibility of connection of both copper and aluminium conductors.
- Resistant to electromagnetic attacks.
- Cut down lightning and switching impulse voltages within the limit of 2000V at current impulses up to 4500A.
- Light indication of voltage presence in power supply circuit.
- Integrated thermal protection (optional). The device disconnects a protected line from the supply- line when temperature in the RCD zone reaches 100+10°C.
- Temporal overvoltage protection. When voltage increases up to the preset limit (from 265 up to 320V - in accordance with the order) the device is disconnected automatically.
- Possibility of remote disconnection of the device (optional) by an external make contact.
- Have modifications without break time lag - of general type, and with time lag - S type
|
|
|
|
|
|
| |
| Type |
Nominal current (In), A |
Number of poles |
Nominal breaking differential current (I∆n), mA |
Nominal make-and-break capacity (Im), A |
Nominal capacity of differential current activation and breaking (I∆m), A |
| RCD-VAD2-10-4-030 |
10 |
4 |
30 |
3000 |
3000 |
| RCD-VAD2-10-4-100 |
10 |
4 |
100 |
3000 |
3000 |
| RCD-VAD2-16-4-030 |
16 |
4 |
30 |
3000 |
3000 |
|
Other versions of RCD can be produced by request, including those with nominal breaking differential current, 300 and 500 mA.
|
|
|
|
|